26• VonDuprinDoorcontrolandsecurityhardware
Alarmedexitdevices
CXTheChexit
®
Door position input: An external door position switch can be
connected to the Chexit.
Using the door position input ensures that the door is in the
closed and latched position before the device rearms.
External inhibit input: This optional input is provided to allow
authorized egress of the Chexit in the armed condition. It also
allows remote reset of the Chexit in an alarmed condition.
Fire alarm input: This input disables the Chexit immediately
upon a fire alarm.
Internal auxiliary lock: The Auxiliary Lock is engaged when the
Chexit is armed. The locking mechanism is specifically designed
to hold securely even when the exit device is struck with forceful
blows.
User defineable rearm time: The Rearm time is the amount of
time aer the device is activated before it arms. It is designed to
give someone time to pass through the door before rearming
oocurs. Timing can be changed by the user for any time between
2 and 28 seconds in two second increments. There is also an
infinite rearm setting that requires the use of an external door
position switch. In this setting the door remains in the rearm
mode until the door is closed. This can be useful on jet way doors
in an airport.
Factory defineable delay time: Most jurisdictions allow 15
seconds of delay before allowing egress. In those cases where 15
seconds is not appropriate, Von Duprin can set the Chexit for any
delay time between 0 and 60 seconds on 2 second increments.
For delays greater than 15 seconds a letter from the local
authority is required.
Chexit typical application
Chexit single door with options – The Chexit is used as an
access control device. The card reader allows access. Also
shown in this application is an external horn and door position
switch. The auxiliary horn is used for increased volume in
remote locations. Using a door position switch gives added
security to the opening in case the door is not reclosed.
With the Chexit disarmed, the opening functions as a normal
exit device. If card readers are required on both sides of the
door, the normally closed contacts of the readers should be
weird in series.
Designed for use on delayed exit applications, the Chexit system is
ideal for controlled areas.
All controls, auxiliary locking, local alarm, and remote signalling are
self-contained in the Chexit, providing safe, secure, easy to install
and simple to operate door control and exit hardware.
Chexit controlled exit device for use on panic or fire exit hardware
applications.
This concept in delayed exit systems combines life safety with the
needs of security and meets all requirements of NFPA 101 for
“special locking arrangement.
The Chexit device includes a 6" x 20" decal for application on door.
“PUSH UNTIL ALARM SOUNDS.
DOOR CAN BE OPENED IN 15 SECONDS
Minimum width door opening:
§ 3' Device 34" opening
§ 4' Device 40" opening
Consult factory for other size requirements.
Solenoid specifications:
§ Continuous duty – 24VDC
§ Current inrush – 16 amperes
§ Current holding – .3 amperes
Requires PS914 Power Supply
Request to exit switch: Built into the device to detect when
someone attempts to exit. Pushing the push pad when the device
is armed will cause this switch to start an irreversible alarm cycle.
Nuisance alarm: When a Chexit is located in a public area, it can be
desireable to limit false alarms. If the Nuisance Delay options are
set to off, the device will go into alarm as soon as the push pad is
touched (when armed). Turning the Nuisance Delay on will require
the push pad to be pressed for 1 second before the Chexit goes into
alarm. If the Nuisance Audible and Nuisance Delay are both on, the
alarm will sound as soon as the push pad is pressed, but the alarm
sequence will stop unless the push pad is held for 1 second or more.
Remote alarm: A relay contact is provided to give external alarm
indication. This contact close when the device is in an irreversible
alarm condition. This contact can be used to drive a horn, lamp, or
other indicative device.
Key switch: The Key switch provides the means to arm, disarm or
reset the Chexit. The key can be removed in either the Arm or
Disarm position.
Indicator lamp: The status of the Chexit can be determined by the
indicator lamp. When the lamp is off, this indicates the device is
disarmed and is functioning as a normal exit device (no delay). A
continuously on lamp indicates the device has just been armed and
as soon as the selectable rearm timer expires, the device will arm.
A slow flashing lamp indicates the device is armed. A fast flashing
indicator lamp indicates the device is in alarm.
Internal horn: Whenever the device is in alarm or the push pad is
pressed the internal horn will sound. The volume level of this horn
exceeds 85 db at 6 feet.
120 VAC 3 x 14 ga.
To Fire Alarm 2 x 18 ga.
2 x 18 ga.
2 x 12 ga.
6 x 18 ga.
2 x 18 ga.
2 x 18 ga.
(new)
KPT-10
EPT
Cable
Chexit
Card
Reader
(Inside or
Outside)
Gnd
Fire Alarm
Card Reader
Door Position
Switch
+24
+24 Red
Black
White
Yellow
Orange
Green
Gray
Violet
Brown
Blue
Chexit
Cable
Gnd
SC
FA
DPS
III
CM+
CM-
NO
C
PS914
Power Supply
2 x 12 ga.
Power Supply
Horn
Horn
–+
Note: Chexit rim or vertical
rod/cable devices lock any
outside trim input when the
device is in the armed
condition. If access is
needed from the trim side
of the door, some type of
electric switch would need
to be tied into the external
inhibit input of the device.
Chexit mortise lock device
the outside trim works
independently from the
Chexit device.